🧩 RTL PID Core Implementation

This chapter explains how the fixed-point PID control equation is mapped directly into Verilog RTL.

The goal is to implement a clear, minimal, and deterministic PID core suitable for ASIC implementation on SKY130.

This design prioritizes explainability over optimization.


🎯 Design Objectives

The PID core is designed to:

This is not a high-performance design, but a transparent educational reference.


🧩 PID Core in System Context

The PID core operates as part of a larger control system, supervised by an FSM and followed by a PWM generator.

In this chapter, the focus is intentionally limited to the PID core itself, independent of supervision and output mapping.

System-level integration and waveform-based verification results are documented in Appendix A: Figure List.


📥 Inputs and Outputs

Inputs

Signal Description
clk Control clock
rst_n Active-low synchronous reset
enable Control enable (from FSM)
v_in Normalized voltage input $V[n]$
i_in Normalized current input $I[n]$ (optional)
v_ref Voltage reference $V_{\text{ref}}[n]$
kp Proportional gain
ki Integral gain
kd Derivative gain

All numeric signals are fixed-point signed values.

Outputs

Signal Description
u_out Control output $u[n]$
valid Output valid flag

🧮 Error Computation (V–I Based)

In this reference design, the control error is defined as:

\[e[n] = V_{\text{ref}}[n] - V[n]\]

Current $I[n]$ is provided as an input and can be incorporated into more advanced control laws, such as:

In this chapter, the voltage error form is used for clarity.


🧠 Internal State Registers

The PID core maintains explicit state registers:

These states are:

There are no implicit or hidden states.


🏗 RTL Pipeline Structure

The PID core can be conceptually divided into four stages:

  1. Error computation
    $e[n] = V_{\text{ref}}[n] - V[n]$

  2. P / I / D term computation
    Fixed-point multiply operations

  3. Summation and scaling
    Alignment and right-shift

  4. Output register
    Registered control output

Each stage uses simple combinational logic followed by registers.

No multi-cycle or variable-latency operations are used.


🧾 Reference Verilog Implementation

The following code illustrates a minimal PID core intended for educational purposes.

module pid_core (
    input  wire        clk,
    input  wire        rst_n,
    input  wire        enable,

    input  wire signed [15:0] v_in,   // Q1.15
    input  wire signed [15:0] i_in,   // Q1.15 (optional)
    input  wire signed [15:0] v_ref,  // Q1.15

    input  wire signed [15:0] kp,
    input  wire signed [15:0] ki,
    input  wire signed [15:0] kd,

    output reg  signed [15:0] u_out,  // Q1.15
    output reg               valid
);

    reg signed [16:0] e_cur;
    reg signed [16:0] e_prev;
    reg signed [31:0] i_acc;

    wire signed [31:0] p_term;
    wire signed [31:0] i_term;
    wire signed [31:0] d_term;

    assign e_cur = v_ref - v_in;

    assign p_term = e_cur * kp;
    assign i_term = i_acc * ki;
    assign d_term = (e_cur - e_prev) * kd;

    always @(posedge clk) begin
        if (!rst_n) begin
            e_prev <= 0;
            i_acc  <= 0;
            u_out  <= 0;
            valid  <= 1'b0;
        end else if (enable) begin
            e_prev <= e_cur;
            i_acc  <= i_acc + e_cur;
            u_out  <= (p_term + i_term + d_term) >>> 15;
            valid  <= 1'b1;
        end else begin
            valid <= 1'b0;
        end
    end

endmodule

This implementation maps directly from the equations defined in the previous chapters.


🚨 Saturation and Safety Considerations

For clarity, saturation logic is omitted in the reference implementation above.

In a production-quality control ASIC, explicit saturation logic is mandatory to guarantee safe operation.

Why Saturation Is Required

Without saturation:

This is especially dangerous in V–I control systems, where excessive voltage or current can damage hardware.


🧯 Integral Windup Protection

The integral accumulator i_acc must be protected against excessive growth.

Typical strategies include:

Example (conceptual)

if (i_acc > I_ACC_MAX)
    i_acc <= I_ACC_MAX;
else if (i_acc < I_ACC_MIN)
    i_acc <= I_ACC_MIN;
else
    i_acc <= i_acc + e_cur;

This logic prevents integrator windup while preserving deterministic timing.


🔒 Output Clamping

The control output u_out must be limited to a safe operating range.

Example (conceptual)

if (u_calc > U_MAX)
    u_out <= U_MAX;
else if (u_calc < U_MIN)
    u_out <= U_MIN;
else
    u_out <= u_calc;

This ensures the PWM generator never receives invalid or dangerous commands.


⏱ Timing Impact

Adding saturation and clamping logic:

Deterministic timing is fully preserved.


🧪 Verification Considerations

RTL verification should include:

All internal registers should be observable in simulation.


🧠 Educational Note

In software, saturation is often hidden in libraries.

In hardware, every limit must be explicit.

This visibility is one of the key educational benefits of implementing control systems as an ASIC.


➡️ Next

Proceed to system-level supervision:

➡️ RTL: FSM & PWM

The next chapter introduces the FSM supervisor, safety handling, and PWM generation logic.